Back close

Resilience-oriented protection scheme for TCSC-compensated line

Publication Type : Journal Article

Publisher : Elsevier

Source : International Journal of Electrical Power & Energy Systems

Url : https://www.sciencedirect.com/science/article/pii/S0142061519336798

Campus : Bengaluru

School : School of Artificial Intelligence

Year : 2020

Abstract : This paper presents a resilience-oriented protection scheme for TCSC-compensated Line. A cross-differential protection scheme is proposed to enhance the resilience of a parallel transmission line (PTL) in the presence of a thyristor controlled series capacitor (TCSC). The faulty phase(s) is (are) identified by estimating the spectral energy of the three-phase currents and computed by applying an efficient powerful signal processing tool known as fast discrete orthonormal S-transform (FDOST). The proposed scheme is widely evaluated against various faults and dynamic power system conditions. The obtained results indicate the proposed resilience-oriented protection scheme is adaptable to different power system scenarios. The scheme precisely classifies the fault with effective discrimination between internal and external faults on a transmission line and a response time of a maximum one cycle from the fault inception.

Cite this Research Publication : Praveen Kumar Mishra, Anamika Yadav, M. Pazoki, “Resilience-Oriented Protection Scheme for TCSC Compensated Line”, International Journal of Electrical Power and Energy Systems, Volume 121, October 2020.

Admissions Apply Now